WVC-GS Pump Radio
WVC-GS Pump Radio
Section titled “WVC-GS Pump Radio”The WVC-GS Pump Radio is a wireless controller designed for remote pump management and monitoring. It enables automated pump control via a latching relay and provides real-time feedback through integrated digital inputs.
Key Features
Section titled “Key Features”- Automated Pump Control: Integrated latching relay for remote start/stop operations.
- Multi-Input Monitoring: 3x Digital Inputs (DI) for monitoring pump status, pressure switches, fault conditions.
- Base Radio Communication: Wireless connectivity to a central Loncel Base Radio for remote monitoring and control.
- Long Range, Low Power: Optimized for reliable performance over large areas with minimal energy consumption.
- Battery Powered: Operates on an 8500mAh Li-SOCl2 3.6V internal battery for long-term deployment.
- Ruggedized Design: Built to withstand harsh outdoor environments.
Technical Specifications
Section titled “Technical Specifications”Connectivity
Section titled “Connectivity”- Wireless Radio: Loncel proprietary long-range wireless
- Frequency: 915MHz ISM band
- Antenna: Integrated omnidirectional antenna
- Range: 1km Line-of-Sight to Base radio or Repeater radio
I/O Capabilities
Section titled “I/O Capabilities”- Digital Inputs: 3x Isolated inputs.
- Suitable for status feedback, alarms, or manual overrides.
- Control Output: 1x Latching Relay
- Designed for low-power switching of pump starters or solenoid pilots.
Electrical
Section titled “Electrical”- Power Source: Battery powered
- Battery Type: 8500mAh Li-SOCl2 (Lithium Thionyl Chloride)
- Operating Voltage: 3.6V DC
- Battery Life: Long-life battery operation suitable for multiple seasons (typically 2-3 years depending on switching frequency)
Mechanical
Section titled “Mechanical”- Mounting: Compact design for pole mounting.
- Enclosure: Weather-proof, industrial-grade housing
Application Overview
Section titled “Application Overview”The WVC-GS Pump Radio is typically installed at pump stations or remote water sources. It allows operators to start and stop pumps remotely via the Loncel platform while simultaneously monitoring critical status inputs such as “Running”, “Fault”, or “Low Pressure”.